100,000 Litre Capacity Self Bunded Double Contained Fuel Storage Tank
The GRANDE100 tank range incorporates double contained self bunded fuel storage with NO self contained pump bay at the front of the unit.
The Grande Tank Range is certified to Australian Standards:
AS1692 - Steel tanks for flammable and combustible liquids
AS1940 - The storage and handling of flammable and combustible liquids
Tanks also comply with ISO (International Standards Organisation) for weight and size on intermodal shipping containers and come complete with standard casting to accommodate the "twistlock" locking system. ISO standards also ensures the fast and easy movement of all Grande Tanks from from ship to rail to truck to site.
Tank Volume: 103,000 litres Safe Fill Level: 98,500 litres Tank Length: 14,630 cm Tank Width: 2,438 cm Tank Height: 3,200 cm Tank Weight: 18,900 Kg
Standard Features and inclusions
Designed to AS 1940
Built to AS1692, CAT-3
Steel self bunded double-wall construction. 6mm internal steel tank with 6mm external steel lining
Sloping floor design for optimised fuel flow from the tank low point
Dual 600mm manway access points for ease of inspection
Up draft venting for tank
Calibrated anodised dipstick
Interstitial space monitoring point with anodized dip stick
6” sockets for installation of submersible pumps.
300 micron minimum white paint finish for increased durability
Set of statutory signage
Incoming Fuel/Product Features
80nb tanker fill point.
Fire safe flanged isolation ball valve and 3"camlock adaptor and cap
Mechanical overfill protection valve.
Internal pipe work.
Electronic high level overfill alarm - hazardous rated with battery powered backup.
Note:
All prices are for bare tanks only
25% deposit required upon order and balance required prior to dispatch
Associated pumping equipment available upon request
PRICE ON APPLICATION - CONTACT US ON 1300 651 391
Warranty Information
Fuel Equipment Specialist warrant all of the FES range of self-bunded tanks, for a period of 84 calendar months for its Structural Integrity, and 12 calendar months for the Painting and Workmanship, provided that :
1. The tanks were installed and operated in accordance to its design and is used according to its normal operating conditions.
2. The tanks receives maintenance and protection by a suitably qualified personnel.
3. The tanks were not subject to negligence, accidents or any form of misuse.
4. Any modifications done without proper consultation to FES will void this warranty.
5. FES’s warranty covers parts only. Labour and Travel costs are not included unless approved by a FES Representative.
For any claims for warranty, the faulty item shall be inspected by FES or its accredited representative prior to any approval of claim or replacement of the equipment.